  Technical Parameter
  (I)

Model No.

FL Lamp Rating

Input Voltage (V)

Input Current (A)

Input Watts (W)

Output Watts
(W)

EB118FL
1 x 18W
240
0.08
20
16.5
EB218FL

2 x 18W

240

0.15

37

33

EB318FL

3 x 18W

240

0.24

58

49.5

EB136FL

1 x 36W

240

0.15

36

33

EB236FL
2 x 36W
240
0.30
72
66
EB336FL
3 x 36W
240
0.45
108
99
EB158FL
1 x 58W
240
0.24
58
53
  (II)

Model No.

FL Lamp Rating

Input Voltage (V)

Input Current (A)

Input Watts (W)

Output Watts
(W)

EB118FL
1 x 18W
120
0.17
20
16.5
EB218FL

2 x 18W

120

0.31

37

33

EB318FL

3 x 18W

120

0.48

58

49.5

EB136FL

1 x 36W

120

0.30

36

33

EB236FL
2 x 36W
120
0.60
72
66
EB336FL
3 x 36W
120
0.90
108
99
EB158FL
1 x 58W
120
0.48
58
53
 

 

Technical Performances

  • The range of input AC voltage (V) 170~265V, 50~60Hz for 240V model; and for 120V & 277V model, the operating voltage range is +/-10%.
  • Operating frequency 30-60kHz
  • Power factor cos>0.98
  • Current harmonic THD=<10%
  • Starting time (s)<2
  • Highest temperature of the casing (tcoc) 70.
  • Environment temperature (taoc) –10 ~ +50.
  • Storage temperature (oC) –40 ~ +85
  • Leakage current (mA)<0.5
  • Lamp current crest factor<1.7
  • Comply with IEC60928, IEC 60929, EN55015, EN61547, IEC61000-3-2, IEC 61000-3-3, IEC61347, SS490.
  • Protection: *Automatic power shutdown against defective lamps
                        *Radio Frequency Interference (RFI) Suppression
                        *MOV surge protection
  • *Dimmable version optional
  • *Input voltage version optional